Input Characteristics | |||
Item |
Requirement |
Unit |
Note |
Ac input voltage range |
85~285 | Vac | 90Vac-264V 850W |
Rated input voltage range |
90~264 | Vac | |
Rated input voltage |
230 | Vac | |
Frequency of ac input voltage |
44 ~ 66(rated 50/60) | Hz | |
power factor | ≥0.90 | Rated input, 100% load | |
Total harmonic of input current | ≤15% | Rated input, 100% load | |
Inrush Current | ≤30 | A | 264Vac/ Normal temperature condition /Rated load |
Max Input Current | ≤10 | A | 185Vac/ Rated load |
Output Characteristics | |||
Item |
Requirement |
Unit |
Note |
Output Voltage Range | 42-55 | Vdc | The monitoring is adjustable, an d all configurations are OK bef ore delivery. After delivery, only communication can be perform ed, but no upgrade or other ope rations can be performed. |
Rated output voltage | 48 | Vdc | If there is no monitoring, the d efault output is 48V. If there is monitoring, the output is adjust ed to 42V | |
Output Current |
0-17.7 | A | ||
Efficiency | ≥92% | 230Vac,50%-100% | ||
temperature coefficient |
±0.02 | %/ºC | ||
Ripple and noise |
≤200 | mVp-p | ≤20MHz 20 MHZ bandwidth or less |
|
Startup time |
≤3 | S | ||
Output rise time | 200 | mS | The output voltage rises from 10% to 90% of the rated voltage for the rated load. |
|
On and off overshoot | ≤±5 | %Vo | Rated input voltage;Output full load. | |
Dynamic | overshoot | ≤ ±5 | %Vo | 25% ~50%,50%~ 75%. 200us,±5%.25% to 50%, 50% to 75% load jump. The recovery time after the dc output voltage change caused by the step change of the load should not exceed 200us, and the overshoot should not exceed ±5% of the output voltage setting value. |
recovery tim e | ≤ 200 | µS | ||
Voltage regulation accuracy |
≤±0.6%*Vo | |||
The telephone balances the noise voltage |
≤2 |
mV |
||
≤50 | 3.4~150KHz |
Broadband noise voltage | ≤20 |
mV |
0.15~30000KHz |
|
Discrete noise |
≤5 | mV |
3.4~150KHz | |
≤3 | 150~200KHz | |||
≤2 | 200~500KHz | |||
≤1 | 500~30000KHz | |||
protective characteristics | ||||
Item |
Requirement |
Unit |
Note |
|
Enter the undervoltage alarm point |
90 |
Vac |
Alarm function, do not perform other operations | |
Input undervoltage protecti on |
80±2 |
Vac |
||
Input the undervoltage recovery point |
85±2 |
Vac |
(90Vac-264Vac) Rated voltage range (90Vac-264Vac) | |
Input overvoltage protection |
290±2 | Vac |
||
Input overvoltage protection recovery point |
280±2 |
Vac |
||
Input frequency protection | <44 >66 < 44 or > 66 |
Hz | Turn off the output, input frequency to normal range, output automatic recovery. |
|
Output overpressure protection | ≥58 | Vdc |
Lock, power off and restart to restore. |