Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 1 Year |
Still deciding? Get samples of $ !
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | rated output voltage(Vdc) | Current range(A) |
output voltage regulating range(Vdc) | Ripple (peak) (rated load, Bandwidth throttling 20MHz) |
G1562 | 65 | 0~61.5 | 55-80 | 350mV |
Input characteristics | |||
Item | technical requirement | unit | notes |
AC input voltage range | 90~264 | Vac |
185Vac~264Vac output full load 4000W; 90Vac~185Vac output power 4000W-1300W linear derating. Please refer to Item 6, 6.2 Input Voltage Output Power Derating Curve for details. |
Rated input voltage range | 185~264 | ||
Rated input voltage | 230 | ||
AC input voltage frequency | 44~66( Rated value is 50/60) | Hz | |
Power factor |
≥0.99 | Rated input, 100% load | |
≥0.98 | Rated input, 50% load | ||
≥0.97 | Rated input, 3% load | ||
Total harmonic of input current |
5% | Rated input, 100% load | |
8% | Rated input, 50% load | ||
12% | Rated input, 30% load | ||
Maximum input current | ≤25 | A | 215Vac, the full load |
inrush current | ≤30 | A | 264Vac,cold state |
output characteristic | |||
Item | technical requirement | unit | notes |
output voltage regulating range | 55-80 | Vdc | Adjustable monitoring |
rated output voltage | 65 | Vdc | |
output current | 0-61.5 | A | Constant power 4000W above 65V, constant current 60 (± 2) A between 55V and 65V |
Peak Efficiency | ≥95% | 230Vac,50%load | |
≥94% | 230Vac,100%load | ||
temperature coefficient | ±0.02 | %/ºC | |
Output ripple and noise | ≤350 | mVp-p | Input 230Vac, output 62Vdc~68Vdc, bandwidth ≤ 20MHz. |
boot time | 3~10 | S | |
Output rise time | ≤200 | mS | The output voltage increases from 10% to 90% at rated load. |
On/off overshoot amplitude | ≤±5 | %Vo | Rated input voltage, output full load. |
Voltage stabilization accuracy | ≤±0.6%*Vo | V | |
Voltage setting accuracy | ≤±0.2 | V | Full output voltage range |
Current setting accuracy | ≤±0.5 | A | 0-61.6 |
Item | technical requirement | unit | notes |
Input undervoltage alarm point | 90 | Vac | Alarm function, no other processing required |
Input undervoltage protection point | 80±2 | Vac | |
Input undervoltage recovery point |
85±2 | Vac | Input voltage range 90Vac-264Vac |
Input overvoltage protection point | 290±2 | Vac | |
Input overvoltage protection recovery point | 280±2 | Vac | |
Input frequency protection | <44 >66 | Hz | Turn off the output, return the input frequency to the normal range, and the output will automatically recover. |
Output Protection | ≥83 | Vdc | Locked, can only be restored after power outage and restart. |
Current limiting protection | 67±2 | A | Hiccup restart, automatic recovery after removal |
Short circuit protection | Hiccup restart, automatic recovery after removal |